Inverter Battery Compatibility: Huawei, Fronius, Sungrow and SolarEdge
A hybrid inverter works only with the batteries its maker approves. Compatible Huawei SUN2000 models take LUNA2000, Fronius GEN24 Plus takes Fronius, BYD or LG batteries, Sungrow SH inverters take Sungrow SBR and SBH batteries, and SolarEdge inverters take SolarEdge Home Battery. If your inverter has no battery input, you can add an AC-coupled battery such as Tesla Powerwall 3.
Checked 5 November 2026 against manufacturer documents.
| Inverter or battery | What the manufacturer documents say (checked 5 November 2026) |
|---|---|
| Huawei SUN2000 KTL-L1, K-LB0, K-LC0, KTL-M1, K-MAP0 and K-MB0 | Huawei LUNA2000-S1. KTL-M1 needs a firmware upgrade first. Huawei Australia's list shows LUNA2000-S0, so confirm which battery applies to you |
| Fronius Primo GEN24 Plus and Symo GEN24 Plus | Fronius Reserva and Reserva Pro, BYD Battery-Box Premium HVS and HVM, LG Flex |
| Sungrow SH hybrid inverters (RS, RT and T models) | Sungrow SBR and SBH batteries only |
| SolarEdge Home Hub, Home Genesis and SExK-AUB inverters | SolarEdge Home Battery for Australia |
| SolarEdge Home Hub 3-Phase inverter | SolarEdge 3-Phase Home Battery |
| Tesla Powerwall 3 | AC-coupled solar can be installed alongside it, up to 5kW AC per Powerwall in the backup circuit (10kW with expansion units) |
How to check if your inverter works with a battery
Find your inverter's model code on its label or in its monitoring app, for example SH10RS, GEN24 Plus or KTL-L1. Then match that code against the manufacturer's approved battery list. Check before you buy. Sungrow, for one, says it may not provide technical support where a non-approved battery is installed.
Verified compatibility chart
This chart lists only pairings we have checked against manufacturer documents. Brands not shown (including Enphase, GoodWe and Sigenergy) are not ruled out. We have not checked them, so confirm them with the manufacturer or your installer.
| Inverter | Phase | Compatible DC-coupled batteries | Limit per inverter |
|---|---|---|---|
| Huawei SUN2000 KTL-L1 | Single | Huawei LUNA2000-S1 | 1 stack, or 2 with SmartAssistant networking |
| Huawei SUN2000-5/6KTL-L1 on Huawei Australia's list | Single | Huawei Australia also lists LUNA2000-5/10/15-S0, so confirm the pairing | Confirm with your installer |
| Huawei SUN2000 K-LB0 | Confirm with your installer | Huawei LUNA2000-S1 | Confirm with your installer |
| Huawei SUN2000 K-LC0 | Confirm with your installer | Huawei LUNA2000-S1 | 2 stacks |
| Huawei SUN2000 KTL-M1 | Three | Huawei LUNA2000-S1, after firmware upgrade | 2 stacks |
| Huawei SUN2000 K-MAP0 | Confirm with your installer | Huawei LUNA2000-S1 | 2 stacks |
| Huawei SUN2000 K-MB0 | Confirm with your installer | Huawei LUNA2000-S1 | 4 stacks |
| Fronius Primo GEN24 Plus (including SC) | Single | Fronius Reserva, Reserva Pro, BYD HVS/HVS+, BYD HVM/HVM+, LG Flex | Up to 4 Reserva or Reserva Pro, up to 3 BYD HVS/HVM |
| Fronius Symo GEN24 Plus (including SC) | Three | Fronius Reserva, Reserva Pro, BYD HVS/HVS+, BYD HVM/HVM+, LG Flex | Up to 4 Reserva or Reserva Pro, up to 3 BYD HVS/HVM (up to 2 HVM 22.1) |
| Sungrow SH5.0 to SH10RS | Single | Sungrow SBR, SBH | Pairing set by Sungrow's cross-reference chart |
| Sungrow SH5.0 to SH10RT, SH15T to SH25T | Three | Sungrow SBR, SBH | Pairing set by Sungrow's cross-reference chart |
| SolarEdge Home Hub Inverter, Home Genesis Inverter | Single | SolarEdge Home Battery for Australia | Up to 3 batteries |
| SolarEdge Residential Three Phase Solar Inverter (SExK-AUB) | Three | SolarEdge Home Battery for Australia | One battery and one inverter per site |
| SolarEdge Home Hub 3-Phase inverter | Three | SolarEdge 3-Phase Home Battery | Confirm with your installer |
Not sure which battery works with your inverter?
One Why Solar Approved installer, one free written quote, and fifteen minutes with a solar expert before you sign.
Huawei inverter battery compatibility
Huawei's LUNA2000-S1 battery works with the SUN2000 models below, and Huawei also lists SUN5000 variants. S1 modules come in 5kWh or 6.9kWh, with up to 20.7kWh usable per stack, and use LiFePO4 cells.
| SUN2000 model | Sizes (kW) | LUNA2000-S1 stacks per inverter |
|---|---|---|
| KTL-L1 | 2, 3, 3.68, 4, 4.6, 5, 6 | 1, or 2 with SmartAssistant networking |
| K-LB0 | 3, 3.68, 4, 4.6, 5, 6 | Confirm with your installer |
| K-LC0 | 8, 10 | 2 |
| KTL-M1 | 3, 4, 5, 6, 8, 10 | 2 |
| K-MAP0 | 5, 6, 8, 10, 12 | 2 |
| K-MB0 | 12, 15, 17, 20, 25 | 4 |
A KTL-M1 must be upgraded to firmware SUN2000MA V100R001C00SPC161 or later before it will work with S1. Older KTL-M0 units are not in the S1 manual's list, so check with Huawei.
S1 or S0 matters here. The list above comes from Huawei's global S1 documents, while Huawei's Australian residential list shows LUNA2000-5, 10 and 15-S0 and the SUN2000-5KTL-L1 and 6KTL-L1. Not every global model is sold in Australia, so confirm your exact inverter and battery codes with Huawei or your installer.
Fronius battery compatibility (GEN24 and Symo)
Fronius's hybrid inverters, the Primo GEN24 Plus (single phase) and Symo GEN24 Plus (three phase), work with Fronius Reserva, Reserva Pro, BYD Battery-Box Premium and LG Flex batteries. The Symo takes the larger sizes.
| Battery | Sizes on Primo and Symo GEN24 Plus | Symo GEN24 Plus only |
|---|---|---|
| Fronius Reserva | 6.3, 9.5 | 12.6 (also Primo GEN24 Plus SC), 15.8 |
| Fronius Reserva Pro | 12.0, 16.0, 20.0 | 24.0, 28.0, 32.0 |
| BYD Battery-Box Premium HVS and HVS+ | 5.1, 7.7 | 10.2, 12.8 |
| BYD Battery-Box Premium HVM and HVM+ | 11.0, 13.8, 16.6, 19.3 | 22.1 |
| LG Flex | 8.6, 12.9 | 17.2 |
You can run up to 4 Reserva or Reserva Pro batteries, or up to 3 BYD HVS or HVM batteries, in parallel on one inverter. The BYD HVM 22.1 is limited to 2 on the Symo.
The BYD HVM 8.3 is not supported on GEN24. The older Symo Hybrid supports BYD HVM only. Fronius's list also has a Verto Plus column, which additionally takes BYD HVB. Fronius says availability depends on country-specific certification and availability, and that inverters should have the latest software update.
The non-hybrid Fronius Primo and Symo (not GEN24) do not appear on Fronius's compatible battery list.
Sungrow battery compatibility
Sungrow SH hybrid inverters work only with Sungrow SBR and SBH high voltage batteries. This covers the SH5.0 to SH10RS (single phase), SH5.0 to SH10RT and SH15T to SH25T (three phase). Sungrow Australia states that other brands of high voltage battery are no longer supported.
Within that range, not every size suits every inverter. Sungrow's SBR and SBH cross-reference chart shows which SBR sizes suit each SH model. Smaller battery stacks can cap charge and discharge power on larger inverters, and some combinations exceed the inverter's voltage range. Ask your installer to show you the pairing they have designed against that chart.
SolarEdge battery compatibility chart
SolarEdge batteries are DC coupled and matched to specific SolarEdge inverters. The SolarEdge Home Battery for Australia (BAT-10K1PS0B-01) has 9.7kWh usable capacity and 5000W continuous power.
Last chance to expand a SolarEdge DC battery stack (November 2026): SolarEdge's installer notice, as reported in November 2026, sets final purchase orders on 20 November 2026 and requires deliveries in Australia by 18 December 2026. After that window, adding a matching SolarEdge Home Battery depends on stock already in the channel. If your installer cannot source a DC-coupled unit in time, an AC-coupled battery (such as Tesla Powerwall 3) is the usual retrofit path, with different wiring and limits. SolarEdge exit and warranty guide.
| SolarEdge inverter | Compatible battery | Limit |
|---|---|---|
| Home Hub Inverter | Home Battery for Australia | Up to 3 batteries per inverter |
| Home Genesis Inverter | Home Battery for Australia | Up to 3 batteries per inverter |
| Residential Three Phase Solar Inverter for Australia (SExK-AUB) | Home Battery for Australia | One battery and one inverter per site |
| Home Hub 3-Phase inverter | 3-Phase Home Battery | Confirm with your installer |
SolarEdge says its 3-Phase Home Battery integrates with the Home Hub 3-Phase inverter only. For backup, the SolarEdge Home Backup Interface enables full or partial backup. These documents cover SolarEdge's own batteries, so get any other pairing confirmed in writing by SolarEdge or your installer before you accept a quote.
Can you use any battery brand?
Not always. It depends on how the battery connects.
A DC-coupled battery connects to a hybrid inverter and must be on that maker's list. Huawei, Fronius, Sungrow and SolarEdge each publish their own pairings, as above.
An AC-coupled battery has its own inverter and sits alongside an existing system. This gives you more room to choose, but your solar system's size still matters, as Tesla's limits below show.
Other brands, such as Varta
We could not confirm a current Varta home battery for Australia. The Varta pulse neo 6 data sheet we opened shows 5.9kWh usable capacity and a 230V AC single phase connection with its own AC charge and discharge rating, but lists country licences for Germany and Austria only. For Varta or any other brand, ask your installer to confirm the battery is approved for Australia and eligible for the federal battery rebate.
Hybrid versus string inverters
A hybrid inverter has a battery input, so a DC-coupled battery connects to it. That limits you to the maker's approved list, as above. A string (non-hybrid) inverter has no battery input. You can add an AC-coupled battery with its own inverter, or replace the inverter with a hybrid. If you are choosing an inverter now, start with our solar inverters section and inverter comparison. Our best solar inverters guide compares the main brands.
Adding a battery to an existing system
Often you can, but how depends on your inverter. If it is a hybrid, you are limited to its maker's batteries. If it is a string inverter, an AC-coupled battery is the usual route.
Tesla says AC-coupled solar can be installed alongside Powerwall 3, most commonly when Powerwall 3 is added to a site with existing solar. Tesla's limit is 5kW AC of AC-coupled solar per Powerwall in the backup circuit (10kW with expansion units). Exceeding it risks damage and voids warranty for the resulting damage. Tesla prefers solar connected directly to Powerwall 3 where possible. Read our Powerwall 3 review, and check the federal battery rebate page for current rules.
Ask why before you sign. Ask your installer why they chose that battery for your inverter, and to put the exact model codes on the quote. Our quote check can help.
Choosing the best battery for your inverter
We do not name one best battery, because the right choice depends on your inverter and your home. The best battery for you meets three tests:
- It is on your inverter maker's approved list.
- It is sized for your usage.
- Your installer can explain why they chose it.
Your inverter sets which batteries are compatible, so savings usually come from comparing like-for-like quotes on the same battery. Compare the options in our solar batteries section and the indicative ranges in our battery price guide, then try our battery calculator.
FAQ
Which batteries work with Huawei SUN2000 inverters?
Huawei LUNA2000-S1 works with SUN2000 KTL-L1, K-LB0, K-LC0, KTL-M1, K-MAP0 and K-MB0 inverters, and a KTL-M1 needs a firmware upgrade first. Huawei's Australian list shows LUNA2000-S0, and not every global model is sold here. Older KTL-M0 units are not in the S1 manual's list. Confirm your exact model with Huawei or your installer.
Which batteries work with Fronius Gen24, Symo and Primo inverters?
Primo GEN24 Plus and Symo GEN24 Plus work with Fronius Reserva and Reserva Pro, BYD Battery-Box Premium HVS and HVM, and LG Flex. Sizes differ by model, and the Symo takes the larger ones. The older Symo Hybrid supports BYD HVM only. Non-hybrid Primo and Symo are not on Fronius's hybrid battery list.
Which batteries are compatible with each Sungrow inverter?
Sungrow SH hybrid inverters work only with Sungrow SBR and SBH high voltage batteries. Sungrow says other brands are no longer supported. Not every size suits every inverter, because its cross-reference chart sets power limits for each pairing. Ask your installer which combination they have designed.
Which batteries work with SolarEdge inverters?
The SolarEdge Home Battery for Australia works with the Home Hub Inverter, Home Genesis Inverter and SExK-AUB three phase inverter. You can fit up to 3 batteries per inverter, but SExK-AUB is limited to one battery and one inverter per site. The SolarEdge 3-Phase Home Battery integrates with the Home Hub 3-Phase inverter only.
Can I use any battery brand with my existing solar system?
Not always. A hybrid inverter needs a DC-coupled battery from its maker's approved list. A string inverter has no battery input, so you would add an AC-coupled battery with its own inverter or replace the inverter. Your installer should confirm which applies to your system.
Can I use a Varta battery?
We could not confirm a current Varta home battery for Australia. The Varta pulse neo data sheet we opened lists country licences for Germany and Austria only. Ask your installer to confirm that any battery is approved for Australia and eligible for the federal battery rebate.
What is the best battery for my inverter?
We do not name one best battery, because the right choice depends on your inverter and your home. The best battery is one on your inverter maker's approved list, sized for your usage, that your installer can explain. Compare like-for-like quotes on the same battery, try our battery calculator and ask why each component was chosen.
Can I add a battery to my existing solar system?
Often yes, but it depends on your inverter. A hybrid inverter limits you to its maker's batteries. A string inverter has no battery input, so you add an AC-coupled battery such as Powerwall 3 with its own inverter, or replace the inverter. Your installer should confirm which applies.
Is my inverter hybrid, and does that change which battery I can use?
Check the model code on the inverter label or in its monitoring app. A hybrid has a battery input and limits you to that maker's approved batteries. Sungrow SH and Fronius GEN24 Plus are hybrids. A string inverter has no battery input, so you need an AC-coupled battery or a new inverter.
Sources
All checked 5 November 2026.
- Huawei, LUNA2000-S1 specifications: https://solar.huawei.com/en/products/luna2000-7-14-21-s1/specs/
- Huawei, LUNA2000-S1 User Manual, issue 06 (30 September 2025): https://solar.huawei.com/dam/asset/view/7fa828aede004fb1b1658929a49d6242.pdf
- Huawei Australia, residential product list: https://solar.huawei.com/au/products/residential/
- Fronius, Compatible batteries for Fronius hybrid inverters: https://www.fronius.com/en/solar-energy/solar-solutions/solar-energy-storage/compatible-batteries
- Sungrow Australia, Approved Batteries with SH Series Hybrid Inverters, AU Version V2 (June 2024): https://service.sungrowpower.com.au/TI_20210824_Approved%20battery%20declaration%20for%20sungrow%20hybrid%20inverters_V16_EN-1.pdf
- Sungrow Australia, SBR and SBH Cross Reference Chart V2.4 (October 2025): https://service.sungrowpower.com.au/New%20knowledge%20base%20file/GD_202510_SBR%20and%20SBH_Cross%20Reference%20Chart_V2.4%20Update%20for%20SBR224%20-%20SBH300.pdf
- SolarEdge, Home Battery for Australia BAT-10K1PS0B-01 datasheet (15 June 2026): https://knowledge-center.solaredge.com/sites/kc/files/se-home-battery-10K1PS0B-01-datasheet-aus.pdf
- SolarEdge Australia, Storage and backup: https://www.solaredge.com/aus/products/residential/storage-and-backup
- Tesla Energy Library, Powerwall 3 install manual (en-au), AC-Coupled Solar System Sizing: https://energylibrary.tesla.com/docs/Public/EnergyStorage/Powerwall/3/InstallManual/BackupGateway/2/en-au/GUID-23D242D1-8D65-47B9-9118-57002FFD84D2.html
- Varta, VARTA pulse neo technical data sheet DB177889DACHEN008: https://www.varta-ag.com/fileadmin/varta/consumer/downloads/energy-storage/varta-pulse-neo/en/Datasheet_pulse_neo_DACH_EN_007.pdf
Not sure which combination is right?
Tell us about your home, your solar setup, and whether you want a battery now or later. We match you with one Why Solar Approved installer who works with the right inverter and battery for your situation, for one free written quote. Before you sign, a solar expert spends fifteen minutes going through it with you.